Ventilation & Exhaust Fans

Supply and extract fans: airflow, motor and bearing condition.

All systems
Preview (draft-3). The risk level comes from draft rule thresholds, and the machine learning advice comes from models trained on synthetic data only. Results are saved here and do not raise tickets or alerts.

Where each parameter is measured

Generic model, so it will differ from your plant. Each number matches a field in the form below, so hover over either one to find it. Confirm instrument positions against your own plant.

Duct Fan Shaft bearing Motor and belt driveRecords 1. Airflow as a share of design 1 2. Motor current as a share of rating 2 3. Fan vibration 3 4. Bearing temperature 4 5. Run hours since last service 5

Drag to rotate, scroll to zoom

  1. 1
    Airflow as a share of design Anemometer traverse or airflow station in the duct, compared with design Healthy: 90 to 110 %
  2. 2
    Motor current as a share of rating Current meter at the motor starter Healthy: up to 95 %
  3. 3
    Fan vibration Portable vibration meter on the fan casing Healthy: up to 4.5 mm/s
  4. 4
    Bearing temperature Contact or infrared thermometer on the fan shaft bearing Healthy: up to 70 °C
  5. 5
    Run hours since last service Run hours from the BMS and the service record Healthy: up to 2200 h