ATLAS AI & Data-Driven Asset Tracking, Lifecycle & Analytics System Ministry of Health Malaysia
FEMS · Electrical

UPS

Uninterruptible supply: battery health, autonomy, loading and output quality.

All systems
Preview (draft-3). The risk level comes from draft rule thresholds, and the machine learning advice comes from models trained on synthetic data only. Results are saved here and do not raise tickets or alerts.

Where each parameter is measured

Generic model, so it will differ from your plant. Each number matches a field in the form below, so hover over either one to find it. Confirm instrument positions against your own plant.

Mains Rectifier InverterTo load Static bypass Battery bank Battery room sensor 1. Measured autonomy as a share of design 1 2. Battery internal resistance rise 2 3. Battery room temperature 3 4. Load as a share of rating 4 5. Output voltage deviation from nominal 5 6. Output voltage total harmonic distortion 6 7. Unplanned transfers to bypass, last 12 months 7

Drag to rotate, scroll to zoom

  1. 1
    Measured autonomy as a share of design Timed discharge test on the battery bank Healthy: at least 90 %
  2. 2
    Battery internal resistance rise Battery analyser on each cell or block Healthy: up to 25 %
  3. 3
    Battery room temperature Temperature sensor in the battery room Healthy: up to 25 °C
  4. 4
    Load as a share of rating Output meter on the UPS panel Healthy: up to 80 %
  5. 5
    Output voltage deviation from nominal Output voltmeter on the UPS panel Healthy: -5 to 5 %
  6. 6
    Output voltage total harmonic distortion Power quality analyser at the UPS output Healthy: up to 5 %
  7. 7
    Unplanned transfers to bypass, last 12 months Event log on the UPS panel Healthy: up to 0