Chilled and condenser water pumps: duty, motor, bearings and seals.

All systems
Preview (draft-3). The risk level comes from draft rule thresholds, and the machine learning advice comes from models trained on synthetic data only. Results are saved here and do not raise tickets or alerts.

Where each parameter is measured

Generic model, so it will differ from your plant. Each number matches a field in the form below, so hover over either one to find it. Confirm instrument positions against your own plant.

Motor Bearings Pump Seal Discharge Suction Strainer Flow meterRecords 1. Flow as a share of design 1 2. Differential head as a share of design 2 3. Motor current as a share of rating 3 4. Pump vibration 4 5. Bearing temperature 5 6. Seal leakage 6 7. Run hours since last service 7

Drag to rotate, scroll to zoom

  1. 1
    Flow as a share of design Flow meter on the discharge pipe, compared with design Healthy: 90 to 110 %
  2. 2
    Differential head as a share of design Pressure gauges on suction and discharge, compared with design head Healthy: 90 to 110 %
  3. 3
    Motor current as a share of rating Current meter at the motor starter or variable speed drive Healthy: up to 95 %
  4. 4
    Pump vibration Portable vibration meter on the bearing housing Healthy: up to 4.5 mm/s
  5. 5
    Bearing temperature Contact or infrared thermometer on the bearing housing Healthy: up to 70 °C
  6. 6
    Seal leakage Visual count of drops at the mechanical seal Healthy: up to 5 drops/min
  7. 7
    Run hours since last service Run hours from the BMS and the service record Healthy: up to 2200 h