Pipeline pressure, supply reserve and quality. This does not replace the area alarm system.
Preview (draft-3). The risk level comes from draft rule thresholds, and the machine learning advice comes from models trained on synthetic data only. Results are saved here and do not raise tickets or alerts.
Where each parameter is measured
Generic model, so it will differ from your plant. Each number matches a field in the form below, so hover over either one to find it. Confirm instrument positions against your own plant.
Drag to rotate, scroll to zoom
-
1
Oxygen pipeline pressure Pressure gauge or alarm panel on the oxygen pipeline Healthy: 380 to 460 kPa
-
2
Medical air pipeline pressure Pressure gauge or alarm panel on the medical air pipeline Healthy: 380 to 460 kPa
-
3
Vacuum below atmospheric Vacuum gauge or alarm panel on the vacuum pipeline Healthy: at least 45 kPa
-
4
Oxygen purity Gas analyser on the oxygen line Healthy: at least 93 %
-
5
Reserve supply remaining Contents gauge on the oxygen tank or reserve manifold Healthy: at least 40 %
-
6
Medical air dew point Dew point sensor after the air dryer Healthy: up to -46 °C
-
7
Pressure drop on leak test Pressure gauge at the zone valve, timed during a leak test Healthy: up to 5 kPa/h