LV Switchboard

Low voltage distribution: connection heat, insulation, loading and supply quality.

All systems
Preview (draft-3). The risk level comes from draft rule thresholds, and the machine learning advice comes from models trained on synthetic data only. Results are saved here and do not raise tickets or alerts.

Where each parameter is measured

Generic model, so it will differ from your plant. Each number matches a field in the form below, so hover over either one to find it. Confirm instrument positions against your own plant.

Incomer Multifunction meter Main breaker Busbars and joints Outgoing breakers 1. Hot spot rise above ambient 1 2. Insulation resistance 2 3. Load as a share of rating 3 4. Current imbalance between phases 4 5. Voltage deviation from nominal 5 6. Voltage total harmonic distortion 6 7. Unplanned breaker trips, last 12 months 7

Drag to rotate, scroll to zoom

  1. 1
    Hot spot rise above ambient Thermal imaging of busbar joints and cable terminations, on load Healthy: up to 25 °C
  2. 2
    Insulation resistance Insulation tester on the isolated busbars, during a shutdown Healthy: at least 100 MΩ
  3. 3
    Load as a share of rating Current meter on the incomer Healthy: up to 80 %
  4. 4
    Current imbalance between phases Phase currents from the incomer multifunction meter Healthy: up to 10 %
  5. 5
    Voltage deviation from nominal Voltmeter on the incomer Healthy: -5 to 5 %
  6. 6
    Voltage total harmonic distortion Power quality analyser on the incomer Healthy: up to 5 %
  7. 7
    Unplanned breaker trips, last 12 months Trip log from breakers or the BMS Healthy: up to 0