Generator
Standby generator readiness: starting, engine condition, fuel and output.
Preview (draft-3). The risk level comes from draft rule thresholds, and the machine learning advice comes from models trained on synthetic data only. Results are saved here and do not raise tickets or alerts.
Where each parameter is measured
Generic model, so it will differ from your plant. Each number matches a field in the form below, so hover over either one to find it. Confirm instrument positions against your own plant.
Drag to rotate, scroll to zoom
-
1
Failed start tests, last 12 months Count from the monthly generator test record Healthy: up to 0
-
2
Starting battery voltage as a share of nominal Multimeter or charger reading at the starting battery Healthy: at least 95 %
-
3
Engine oil pressure on load Oil pressure gauge on the engine control panel Healthy: at least 280 kPa
-
4
Coolant temperature on load Coolant temperature sensor at the engine outlet or radiator Healthy: up to 95 °C
-
5
Fuel reserve remaining Level gauge on the day tank Healthy: at least 50 %
-
6
Load as a share of rating kW meter on the generator control panel, on load test Healthy: up to 80 %
-
7
Output voltage deviation from nominal Voltmeter on the generator control panel, on load Healthy: -5 to 5 %
-
8
Output frequency deviation from nominal Frequency meter on the generator control panel, on load Healthy: -1 to 1 %
-
9
Run hours since last service Hour meter on the control panel and the service record Healthy: up to 250 h