FEMS · Mechanical
All systems
Critical Area Ventilation
Theatres, isolation rooms and ICUs. This does not replace the room pressure alarm.
Preview (draft-3). The risk level comes from draft rule thresholds, and the machine learning advice comes from models trained on synthetic data only. Results are saved here and do not raise tickets or alerts.
Where each parameter is measured
Generic model, so it will differ from your plant. Each number matches a field in the form below, so hover over either one to find it. Confirm instrument positions against your own plant.
Drag to rotate, scroll to zoom
-
1
Pressure difference to the next area, in the designed direction Room pressure monitor across the door to the next area Healthy: at least 8 Pa
-
2
Air changes per hour Flow hood or duct airflow divided by the room volume Healthy: at least 12 per hour
-
3
HEPA filter differential pressure Differential pressure gauge across the HEPA filter Healthy: up to 400 Pa
-
4
Room temperature Room temperature sensor on the wall, away from the supply air Healthy: 20 to 24 °C
-
5
Room relative humidity Room humidity sensor on the wall, away from the supply air Healthy: 40 to 60 %
History
No screenings yet for this system.