FEMS · Mechanical
All systems
Cooling Tower
Heat rejection performance, fan condition and water hygiene.
Preview (draft-3). The risk level comes from draft rule thresholds, and the machine learning advice comes from models trained on synthetic data only. Results are saved here and do not raise tickets or alerts.
Where each parameter is measured
Generic model, so it will differ from your plant. Each number matches a field in the form below, so hover over either one to find it. Confirm instrument positions against your own plant.
Drag to rotate, scroll to zoom
-
1
Water temperature leaving the tower Temperature sensor on the pipe leaving the basin Healthy: up to 32 °C
-
2
Water temperature entering the tower Temperature sensor on the hot water pipe entering the tower
-
3
Outdoor wet bulb temperature Wet bulb sensor outdoors, near the air intake and out of direct sun
-
4
Fan vibration Vibration sensor or portable meter on the fan gearbox or motor Healthy: up to 4.5 mm/s
-
5
Water conductivity Conductivity probe in the basin or on the bleed line Healthy: up to 1500 µS/cm
-
6
Total bacterial count Dip slide test on a water sample from the basin Healthy: up to 10000 CFU/mL
-
7
Legionella count Laboratory culture of a water sample from the basin Healthy: up to 100 CFU/L
-
8
Run hours since last service Fan run hours from the BMS and the service record Healthy: up to 2200 h
Tower approach to wet bulb is calculated, not measured: leaving water temperature minus wet bulb temperature.
Tower cooling range is calculated, not measured: entering water temperature minus leaving water temperature.
History
No screenings yet for this system.