ATLAS AI & Data-Driven Asset Tracking, Lifecycle & Analytics System Ministry of Health Malaysia
FEMS · Mechanical

Chiller

Water-cooled chillers: cooling output, heat transfer, oil and compressor condition.

All systems
Preview (draft-3). The risk level comes from draft rule thresholds, and the machine learning advice comes from models trained on synthetic data only. Results are saved here and do not raise tickets or alerts.

Where each parameter is measured

Generic model, so it will differ from your plant. Each number matches a field in the form below, so hover over either one to find it. Confirm instrument positions against your own plant.

Condenser Evaporator Condenser water Chilled water Expansion valve Compressor Motor Oil systemRecords 1. Chilled water supply temperature 1 2. Chilled water return temperature 2 3. Evaporator approach 3 4. Condenser approach 4 5. Oil differential pressure 5 6. Motor current as a share of rating 6 7. Compressor vibration 7 8. Run hours since last service 8

Drag to rotate, scroll to zoom

  1. 1
    Chilled water supply temperature Temperature sensor on the chilled water pipe leaving the evaporator Healthy: 5.5 to 8 °C
  2. 2
    Chilled water return temperature Temperature sensor on the chilled water pipe entering the evaporator
  3. 3
    Evaporator approach Chiller panel: leaving water temperature minus evaporator refrigerant temperature Healthy: up to 2 °C
  4. 4
    Condenser approach Chiller panel: condenser refrigerant temperature minus leaving water temperature Healthy: up to 2.5 °C
  5. 5
    Oil differential pressure Oil pressure transducers across the oil pump and filter, shown on the chiller panel Healthy: at least 170 kPa
  6. 6
    Motor current as a share of rating Current meter on the chiller panel or motor starter Healthy: up to 95 %
  7. 7
    Compressor vibration Portable vibration meter on the compressor bearing housing Healthy: up to 4.5 mm/s
  8. 8
    Run hours since last service Run hour counter on the chiller panel and the service record Healthy: up to 2200 h

Chilled water temperature rise is calculated, not measured: return temperature minus supply temperature.

Simulation
Fault patterns
Choose a scenario to fill every field, then run the screening.

Chilled water temperature rise is calculated from your readings. Normal: 4 to 7 °C.

History

No screenings yet for this system.