ATLAS AI & Data-Driven Asset Tracking, Lifecycle & Analytics System Ministry of Health Malaysia
FEMS · Mechanical

Air Handling Unit

Supply air condition, airflow, filters and fan condition.

All systems
Preview (draft-3). The risk level comes from draft rule thresholds, and the machine learning advice comes from models trained on synthetic data only. Results are saved here and do not raise tickets or alerts.

Where each parameter is measured

Generic model, so it will differ from your plant. Each number matches a field in the form below, so hover over either one to find it. Confirm instrument positions against your own plant.

Air handling unit Air in Filter Coil Fan RoomSupply duct Chilled water valveRecords 1. Supply air temperature 1 2. Served room relative humidity 2 3. Airflow as a share of design 3 4. Filter differential pressure 4 5. Chilled water valve opening 5 6. Fan vibration 6 7. Run hours since last service 7

Drag to rotate, scroll to zoom

  1. 1
    Supply air temperature Temperature sensor in the supply duct after the fan Healthy: 12 to 16 °C
  2. 2
    Served room relative humidity Humidity sensor in the served room or return duct Healthy: 40 to 65 %
  3. 3
    Airflow as a share of design Airflow station or balancing measurement in the supply duct, compared with design Healthy: 90 to 110 %
  4. 4
    Filter differential pressure Differential pressure gauge across the filter bank Healthy: up to 250 Pa
  5. 5
    Chilled water valve opening Valve position feedback from the actuator or BMS Healthy: up to 85 %
  6. 6
    Fan vibration Portable vibration meter on the fan bearing housing Healthy: up to 4.5 mm/s
  7. 7
    Run hours since last service Fan run hours from the BMS and the service record Healthy: up to 2200 h
Simulation
Fault patterns
Choose a scenario to fill every field, then run the screening.

History

No screenings yet for this system.