FEMS · Mechanical
All systems
Air Handling Unit
Supply air condition, airflow, filters and fan condition.
Preview (draft-3). The risk level comes from draft rule thresholds, and the machine learning advice comes from models trained on synthetic data only. Results are saved here and do not raise tickets or alerts.
Where each parameter is measured
Generic model, so it will differ from your plant. Each number matches a field in the form below, so hover over either one to find it. Confirm instrument positions against your own plant.
Drag to rotate, scroll to zoom
-
1
Supply air temperature Temperature sensor in the supply duct after the fan Healthy: 12 to 16 °C
-
2
Served room relative humidity Humidity sensor in the served room or return duct Healthy: 40 to 65 %
-
3
Airflow as a share of design Airflow station or balancing measurement in the supply duct, compared with design Healthy: 90 to 110 %
-
4
Filter differential pressure Differential pressure gauge across the filter bank Healthy: up to 250 Pa
-
5
Chilled water valve opening Valve position feedback from the actuator or BMS Healthy: up to 85 %
-
6
Fan vibration Portable vibration meter on the fan bearing housing Healthy: up to 4.5 mm/s
-
7
Run hours since last service Fan run hours from the BMS and the service record Healthy: up to 2200 h